LF Series. These heaters have an ethylene glycol / water mixture heat transfer medium.
LF Series. These heaters have an ethylene glycol / water mixture heat transfer medium in combination with a permanently sealed, liquid to air heat exchanger. Capacities range from 25,600 to 85,370 BTU per hour.
FEATURES
- For NEC Class I, Groups B, C and D and Class II, Groups E, F and G
- UL or FM Listed
- For NEC Temperature Codes T1 to T3B
- Heating Capacities from 6,140 to 119,450 BTU/HR
- Choice of Floor, Wall or Ceiling Mounted Models
- Optional Thermostats, Humidistats and Disconnects
LIQUID-TO-AIR, FORCED AIR (LF) HEATERS FOR CEILING OR WALL (CW) INSTALLTION
Ident No. | Model | Heat | KW | Voltage | AMPS | Height | Width | Depth | Weight |
---|---|---|---|---|---|---|---|---|---|
T3B | 1024LF-208/1-CW-ID1-T3B | 10250 | 3.0 | 208/1 | 15.3 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 1024LF-208/3-CW-ID1-T3B | 10250 | 3.0 | 208/3 | 8.9 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 1024LF-240/1-CW-ID1-T3B | 10250 | 3.0 | 240/1 | 13.5 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 1024LF-240/3-CW-ID1-T3B | 10250 | 3.0 | 240/3 | 7.9 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 1024LF-480/3-CW-ID1-T3B | 10250 | 3.0 | 480/3 | 3.9 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 1707LF-208/3-CW-ID1-T3B | 17050 | 5.0 | 208/3 | 14.4 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 1707LF-240/3-CW-ID1-T3B | 17050 | 5.0 | 240/3 | 12.7 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 1707LF-480/3-CW-ID1-T3B | 17050 | 5.0 | 480/3 | 6.4 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 2561LF-208/3-CW-ID1-T3B | 25600 | 7.5 | 208/3 | 21.4 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 2561LF-240/3-CW-ID1-T3B | 25600 | 7.5 | 240/3 | 18.7 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 2561LF-480/3-CW-ID1-T3B | 25600 | 7.5 | 480/3 | 9.4 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 3415LF-208/3-CW-ID1-T3B | 34100 | 10.0 | 208/3 | 28.3 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 3415LF-240/3-CW-ID1-T3B | 34100 | 10.0 | 240/3 | 24.7 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 3415LF-480/3-CW-ID1-T3B | 34100 | 10.0 | 480/3 | 12.4 | 18-1/2 | 24-1/2 | 23 | 151 |
T3B | 5122LF-208/3-CW-ID1-T3B | 51200 | 15.0 | 208/3 | 41.4 | 22-1/2 | 28-1/2 | 23 | 173 |
T3B | 5122LF-240/3-CW-ID1-T3B | 51200 | 15.0 | 240/3 | 36.0 | 22-1/2 | 28-1/2 | 23 | 173 |
T3B | 5122LF-480/3-CW-ID1-T3B | 51200 | 15.0 | 480/3 | 18.0 | 22-1/2 | 28-1/2 | 23 | 173 |
T3B | 6830LF-480/3-CW-ID1-T3B | 68250 | 20.0 | 480/3 | 24.0 | 22-1/2 | 28-1/2 | 23 | 173 |
T3B | 8537LF-480/3-CW-ID1-T3B | 85300 | 25.0 | 480/3 | 30.1 | 26-1/2 | 32-1/2 | 23 | 204 |
T3B | 10235LF-480/3-CW-ID1-T3B | 102350 | 30.0 | 480/3 | 36.1 | 26-1/2 | 32-1/2 | 23 | 204 |
T3B | 11945LF-480/3-CW-ID1-T3B | 119450 | 35.0 | 480/3 | 42.1 | 26-1/2 | 32-1/2 | 23 | 204 |